Relay Module KFD0-RO-Ex2

KFD0-RO-Ex2
  • 2-channel isolated barrier
  • 24 V DC supply (loop powered)
  • Logic input 15 V DC ... 30 V DC, non-polarized
  • Relay contact output
  • Up to SIL 3 acc. to IEC/EN 61508

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Uddrag af datablad: Tekniske data for   KFD0-RO-Ex2

General specifications
Signal typeDigital Output
Functional safety related parameters
Safety Integrity Level (SIL)SIL 3
Supply
Rated voltage15 ... 30 V DC , loop powered
Power dissipation0.8 W
Input
Connection sidecontrol side
Connectionterminals 7, 8, 9
Input voltage15 ... 30 V DC
Input current≤ 21 mA per channel
Output
Safety noteAttention! Combination of output Ex i with output not Ex i is not permitted.
If load voltage > 50 V, de-energize before removing the terminals.
Connection sidefield side
Connectionterminals 1, 2, 3; 4, 5, 6
Contact loading230 V AC/2 A/cos φ > 0.7; 40 V DC/2 A resistive load
Energized/De-energized delayapprox. 10 ms / approx. 5 ms
Mechanical life5 x 106 switching cycles
Transfer characteristics
Switching frequency< 10 Hz
Galvanic isolation
Input/Outputreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output/Outputbasic insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Indicators/settings
Display elementsLEDs
Labelingspace for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Low voltage
Directive 2014/35/EUEN 61010-1:2010
Conformity
Electromagnetic compatibilityNE 21:2006
Degree of protectionIEC 60529:2001
Ambient conditions
Ambient temperature-20 ... 65 °C (-4 ... 149 °F)
Mechanical specifications
Degree of protectionIP20
Connectionscrew terminals
Massapprox. 100 g
Dimensions20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) (W x H x D) , housing type B2
Height119 mm
Width20 mm
Depth115 mm
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
EU-type examination certificateDMT 00 ATEX E 016
MarkingEx-Hexagon II (1)G [Ex ia Ga] IIC
Ex-Hexagon II (1)D [Ex ia Da] IIIC
Ex-Hexagon I (M1) [Ex ia Ma] I
OutputEx ia
Voltage60 V
Current2 A
Input
Maximum safe voltage40 V DC (Attention! Um is no rated voltage.)
Output
Contact loading50 V AC/2 A ; 40 V DC/2 A (TÜV 00 ATEX 1621 X)
CertificateTÜV 00 ATEX 1621 X
MarkingEx-Hexagon II 3G Ex nA nC IIC T4
Galvanic isolation
Input/Outputsafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Output/Outputsafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 60 V
Directive conformity
Directive 2014/34/EUEN IEC 60079-0:2018+AC:2020 , EN 60079-11:2012 , EN 60079-15:2010
International approvals
FM approval
Control drawing116-0261
CSA approval
Control drawing116-0156
IECEx approval
IECEx certificateIECEx BVS 10.0025
IECEx marking[Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027210101
ECLASS 12.027210101
ECLASS 11.027210101
ECLASS 10.0.127210101
ECLASS 9.027210101
ECLASS 8.027210101
ECLASS 5.127210121
ETIM 9.0EC001485
ETIM 8.0EC001485
ETIM 7.0EC001485
ETIM 6.0EC001485
ETIM 5.0EC001485
UNSPSC 12.139121543

Details: KFD0-RO-Ex2

Datasheet: KFD0-RO-Ex2

DatasheetFil typeFil størrelse
Datasheet KFD0-RO-Ex2PDF959 KB
Fiche de données KFD0-RO-Ex2PDF963 KB
Datenblatt KFD0-RO-Ex2PDF961 KB
Datasheet KFD0-RO-Ex2PDF1012 KB
Hoja de datos KFD0-RO-Ex2PDF965 KB

Documents: KFD0-RO-Ex2

ManualsFil typeFil størrelse
ManualPDF3685 KB
HandbuchPDF3693 KB
Instruction manuals
ИнструкцииPDF170 KB
Instruction manual / BetriebsanleitungPDF330 KB
Návod k poużitíPDF165 KB
Instruktions manualPDF163 KB
Instruction manualPDF169 KB
KasutusjuhendPDF160 KB
KäyttöohjePDF160 KB
Manuel d'instructionsPDF166 KB
BetriebsanleitungPDF171 KB
Οδηγίες χρήσηςPDF174 KB
HandleidingPDF165 KB
Instruction manual / BetriebsanleitungPDF163 KB
Használati útmutatóPDF166 KB
Manuale di istruzioniPDF165 KB
Lietošanas pamācībaPDF163 KB
Instrukciju vadovasPDF165 KB
Instrukcja obsługiPDF167 KB
Manual de instruçõesPDF166 KB
Manual de utilizarePDF165 KB
Návod na poużitiePDF165 KB
Navodila za uporaboPDF162 KB
Manual de instruccionesPDF166 KB
ManualPDF161 KB
Application reports
Application Report - Biological Cleaning of Wastwater and Secondary Sedimentation StagePDF566 KB
Application Report - Energy Generation in Wastwater Treatment PlantsPDF532 KB
Application Report - Generating Electricity in Coal-Fired Power PlantsPDF412 KB
Application Report - Sand Trap and Preliminary Sedimentation StagePDF448 KB
Application Report - Screening Systems in Sewage Treatment PlantsPDF577 KB
Application Report - Sicherer Brennstofftransport in KohlekraftwerkenPDF391 KB
Application Report - Water Inlet in Wastewater Treatment PlantsPDF526 KB
Applikationsbericht - Biologische Abwasserreinigung und NachklärungPDF568 KB
Applikationsbericht - Energiegewinnung in KläranlagenPDF535 KB
Applikationsbericht - Rechenanlagen in KläranlagenPDF578 KB
Applikationsbericht - Sandfang und VorklärungPDF434 KB
Applikationsbericht - Sicherer Brennstofftransport in KohlekraftwerkenPDF393 KB
Applikationsbericht - Stromerzeugung in KohlekraftwerkenPDF416 KB
Applikationsbericht - Wasserzulauf in KläranlagenPDF527 KB
Documents
Functional Safety ManualPDF415 KB

CAD+CAE: KFD0-RO-Ex2

CADFil typeFil størrelse
CAD 3-D / CAD 3-DSTP2510 KB
CAD Portal / CAD PortalLINK---
EPLAN
CAE EPLAN Data Portal / CAE EPLAN Data PortalLINK---
CAE EPLAN macro EDZ / CAE EPLAN Makro EDZEDZ1175 KB

Tilhørende produkter: KFD0-RO-Ex2

Matching System Components
Cable trunking is integrated in the mounting profile, Safe spacious separation of safe and hazardous signals, No additional cable guides necessary, Standard length 1.8 m (5.8 ft), simple to customize to application space, With mounting aidspa
Accessories
3-pin screw terminal, For KF modules of K-System, Packaging unit: 5 pieces greenpa
Coding of K-System terminal blocks, Coding of LB/FB-System front sockets, Packaging unit: 20 x 6 coding pinspa
Safety Products Selector

Choose from various selection criteria like safety integrity level, performance level, device function, and signal type and find the SIL/PL assessed device that you are looking for.