Uddrag af datablad: Tekniske data for   KFD0-SD2-Ex1.10100

General specifications
Signal typeDigital Output
Functional safety related parameters
Safety Integrity Level (SIL)SIL 3
Supply
Rated voltage20 ... 35 V DC , loop powered
Power dissipation< 1.2 W (Ui ≤ 30 V)
Input
Connection sidecontrol side
Connectionterminals 7, 8
Rated voltage20 ... 35 V DC
Current150 mA at 20 V input voltage, load = 100 Ω
100 mA at 35 V input voltage, load = 100 Ω
Output
Connection sidefield side
Connectionterminals 1+, 2-
Internal resistor≤ 68 Ω
Current≥ 100 mA
Voltage≥ 9.5 V
Open loop voltagemin. 16.2 V
Output current100 mA
Output signalThese values are valid for the rated operating voltage 20 ... 35 V DC.
Energized/De-energized delaysingle operation: typ. 1.7 ms/50 µs; periodical: typ. 5 µs/50 µs
Indicators/settings
Display elementsLED
Labelingspace for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Conformity
Electromagnetic compatibilityNE 21:2006
Degree of protectionIEC 60529:2001
Protection against electrical shockUL 61010-1:2004
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protectionIP20
Connectionscrew terminals
Massapprox. 100 g
Dimensions20 x 107 x 115 mm (0.8 x 4.2 x 4.5 inch) (W x H x D) , housing type B1
Height107 mm
Width20 mm
Depth115 mm
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
EU-type examination certificateBASEEFA 06 ATEX 0252
MarkingEx-Hexagon II (1)G [Ex ia Ga] IIC
Ex-Hexagon II (1)D [Ex ia Da] IIIC
Ex-Hexagon I (M1) [Ex ia Ma] I
Voltage17 V
Current271 mA
Power1152 mW
Input
Maximum safe voltage250 V (Attention! The rated voltage can be lower.)
CertificateTÜV 99 ATEX 1499 X
MarkingEx-Hexagon II 3G Ex nA II T4
Galvanic isolation
Input/Outputsafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 2014/34/EUEN IEC 60079-0:2018+AC:2020 , EN 60079-11:2012 , EN 60079-15:2010
International approvals
FM approval
Control drawing116-0309
UL approvalE106378
Control drawing116-0316 (cULus)
IECEx approval
IECEx certificateIECEx BAS 06.0058
IECEx CML 19.0093X
IECEx marking[Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I
Ex ec IIC T4 Gc
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027210101
ECLASS 12.027210190
ECLASS 11.027210190
ECLASS 10.0.127210190
ECLASS 9.027210190
ECLASS 8.027210190
ECLASS 5.127210121
ETIM 9.0EC001485
ETIM 8.0EC001485
ETIM 7.0EC001485
ETIM 6.0EC001485
ETIM 5.0EC001485
UNSPSC 12.139121008

Details: KFD0-SD2-Ex1.10100

Datasheet: KFD0-SD2-Ex1.10100

DatasheetFil typeFil størrelse
Datasheet KFD0-SD2-Ex1.10100PDF1094 KB
Fiche de données KFD0-SD2-Ex1.10100PDF1100 KB
Datenblatt KFD0-SD2-Ex1.10100PDF1098 KB
Datasheet KFD0-SD2-Ex1.10100PDF1145 KB
Hoja de datos KFD0-SD2-Ex1.10100PDF1103 KB

Documents: KFD0-SD2-Ex1.10100

ManualsFil typeFil størrelse
ManualPDF3685 KB
HandbuchPDF3693 KB
Instruction manuals
ИнструкцииPDF172 KB
Instruction manual / BetriebsanleitungPDF331 KB
Návod k poużitíPDF167 KB
Instruktions manualPDF166 KB
Instruction manualPDF171 KB
KasutusjuhendPDF163 KB
KäyttöohjePDF162 KB
Manuel d'instructionsPDF168 KB
BetriebsanleitungPDF172 KB
Οδηγίες χρήσηςPDF176 KB
HandleidingPDF167 KB
Instruction manual / BetriebsanleitungPDF166 KB
Használati útmutatóPDF168 KB
Manuale di istruzioniPDF166 KB
Lietošanas pamācībaPDF166 KB
Instrukciju vadovasPDF167 KB
Instrukcja obsługiPDF169 KB
Manual de instruçõesPDF167 KB
Manual de utilizarePDF167 KB
Návod na poużitiePDF167 KB
Navodila za uporaboPDF165 KB
Manual de instruccionesPDF168 KB
ManualPDF164 KB
Technical information
Application Guideline Solenoid DriversPDF734 KB
Anwendungsbeschreibung VentilsteuerbausteinePDF737 KB
Application reports
Application Report - Energy Generation in Wastwater Treatment PlantsPDF532 KB
Application Report - Generating Electricity in Coal-Fired Power PlantsPDF412 KB
Application Report - Screening Systems in Sewage Treatment PlantsPDF577 KB
Application Report - Sicherer Brennstofftransport in KohlekraftwerkenPDF391 KB
Application Report - Water Inlet in Wastewater Treatment PlantsPDF526 KB
Applikationsbericht - Energiegewinnung in KläranlagenPDF535 KB
Applikationsbericht - Rechenanlagen in KläranlagenPDF578 KB
Applikationsbericht - Sicherer Brennstofftransport in KohlekraftwerkenPDF393 KB
Applikationsbericht - Stromerzeugung in KohlekraftwerkenPDF416 KB
Applikationsbericht - Wasserzulauf in KläranlagenPDF527 KB
Documents
Safety ManualPDF414 KB

CAD+CAE: KFD0-SD2-Ex1.10100

CADFil typeFil størrelse
CAD 3-D / CAD 3-DSTP105 KB
CAD Portal / CAD PortalLINK---
EPLAN
EPLAN macro EDZ / EPLAN Makro EDZEDZ46 KB

Tilhørende produkter: KFD0-SD2-Ex1.10100

Matching System Components
Cable trunking is integrated in the mounting profile, Safe spacious separation of safe and hazardous signals, No additional cable guides necessary, Standard length 1.8 m (5.8 ft), simple to customize to application space, With mounting aidspa
Accessories
3-pin screw terminal, For KF modules of K-System, Packaging unit: 5 pieces greenpa
3-pin screw terminal, For KF modules of K-System, Packaging unit: 5 pieces bluepa
Coding of K-System terminal blocks, Coding of LB/FB-System front sockets, Packaging unit: 20 x 6 coding pinspa
Safety Products Selector

Choose from various selection criteria like safety integrity level, performance level, device function, and signal type and find the SIL/PL assessed device that you are looking for.